Slide background

FAQ

F.A.Q. return

This space is for you to search for answers to frequently asked questions on electrical hookups.

 

No. This nominal gauge must not be confused with a geometric gauge (the cross section area).

The nominal gauge is linked to its maximum value of electrical resistance at 20º C (.../km) and, in many cases; it is also complemented by other characteristics, such as the minimum quantity of wires or the maximum gauge of wires it is made from.

The nominal gauge is defined in square millimeters, based on the IEC standard (International Electrotechnical Commission), the specific Brazilian standard is NBR NM 280, based on the conductor classification.

It depends on the use. The only difference is flexibility, as the current capacity is the same, for example, a 1.5 mm2 wire, 1.5 mm2 cable, or 1.5 mm2 flexible cable have the same current conductive capacity.

Then to summarize, the current capacity is the same for all the nominal gauges, regardless of the class of conductor.

The preference of the designer or installer will define the class selection.

Yes, there is. Light blue must be used for neutral conductors, and green or green/yellow for grounding conductors, also known as "Little Brazil" as they are the Brazilian national colors.

The other colors may be freely chosen. This rule is defined by the NBR 5410 Brazilian technical standard - Low voltage electrical hookups.

Based on the NBR 5410 technical standard, the minimum gauge for electrical outlets for general use is 2.5mm² and for lighting circuits, it is 1.5mm².

There is no problem in using a larger nominal gauge; but it just cannot be smaller.

The class defines if the conductor is a wire, (rigid) cable, or a (flexible) cable.

Class 1 is applied to solid wires and class 2 is applied to rigid cables.

Classes 4 and 5 are applied to flexible cables, as class 5 is more flexible than class 4, however the difference is not always noticeable.

AWG means (American Wire Gauge) which is the standardized American scale. Use the conversion table below to convert to the AWG standard to mm², which then converts to the EB-98 standard, which has already been canceled and substituted by the NBR NM 280 standard, which has become the currently applied standard, both issued by ABNT (the Brazilian Standardization Entity).

This table is not valid for conversions based on the NEC table - National Electrical Code, which complies with the American standard.

Tabela de Conversão

AWG

mm²

20

0,5

18

0,75

16

1

14

1,5

12

2,5

10

4

8

6

6

10

4

16

2

25

1

35

1/0

50

3/0

70

250

95

300

120

350

150

500

152

600

240

800

300

The table below was taken from the NBR 5410:2004 standard, which describes the current capacity in amperes (A), for PVC insulated copper conductors (70°C), based on the B1 and B2 reference methods.

B1: insulated conductors or unipolar cables in round conduits embedded in brickwork.

B2: multipolar cable in round conduits embedded in brickwork.

SEÇÃO NOMINAL
mm²

B1

B2

2
CONDUTORES
CARREGADOS

3
CONDUTORES
CARREGADOS

2
CONDUTORES
CARREGADOS

3
CONDUTORES
CARREGADOS

0,5

9

8

9

8

0,75

11

10

11

10

1

14

12

13

12

1,5

17,5

15,5

16,5

15

2,5

24

21

23

20

4

32

28

30

27

6

41

36

38

34

10

57

50

52

46

16

76

68

69

62

25

101

89

90

80

35

125

110

111

99

50

151

134

133

118

70

192

171

168

149

95

232

207

201

179

120

269

239

232

206

150

309

275

265

236

185

353

314

300

268

240

415

370

351

313

300

477

426

401

358

400

571

510

477

425

500

656

587

545

486

The voltage drop cannot be over 4% in a terminal circuit, however in higher voltage equipment with a higher initial voltage, during the initial starting period the voltage drop can be greater, as long as the permissible limits comply with the respective standards.

See the voltage drop table below on insulated PVC products operating at 70°C and room temperature at 30°C, installed as stated in the B1 reference method.

Seção nominal (mm²)

Queda de tensão para cos Ø = 0,8 (V/A.km)

Conduto não-magnético

Conduto Magnético

 

Circuito monofásico

Circuito trifásico

1,5

23,3

20,2

23

2,5

14,3

12,4

14

4

8,96

7,79

9

6 6,03 5,25 5,87

10

3,63

3,17

3,54

16

2,32

2,03

2,27

25

1,51

1,33

1,5

35

1,12

0,98

1,12

50 0,85 0,76 0,86

70

0,62

0,55

0,64

95

0,48

0,43

0,5

120

0,40

0,36

0,42

150

0,35

0,31

0,37

185

0,30

0,27

0,32

240

0,26

0,23

0,29


For further information, get in touch with SIL at the following e-mail address:

Technical Questions